MSC Signal Conditioners - Spec

Models

Model Number

Source

Destination

MSC-TC-V

Thermocouple

Voltage

MSC-TC-C

Thermocouple

Current

MSC-RTD-V

RTD

Voltage

MSC-RTD-C

RTD

Current

MSC-V-V

Voltage

Voltage

MSC-V-C

Voltage

Current

MSC-C-V

Current

Voltage

MSC-C-C

Current

Current

MSC-POT-V

Potentiometer

Voltage

MSC-POT-C

Potentiometer

Current

MSC-FRQ-V

Frequency

Voltage

MSC-FRQ-C

Frequency

Current

MSC-LI-C

Current
(Loop Powered)

Current
(Loop Powered)

Dimensions

Dimensions 88mm (H) x 68mm (D) x 12mm (W) 3
5 in (H) x 2.7 in (D) x .48 in (W)
Weight 40 g/1.4 oz. 
Humidity 95% non-condensing 
Mounting DIN rail (32mm-G and 35mm-H) 
Terminals Screw Terminals accept 14-22 AWG  

Specifications - MSC and MSP

Accuracy  0.05% F.S. (includes linearity, repeatability and calibration errors) 
 Drift 0.01% F.S. per °C (offset + gain) 
 CJC Acc. 0.2°C over 15 to 55°C (ambient) 
 Resolution 16 bits <1.0°C over -40 to 15°C
<.3°C over 55 to 75°C
 Isolation 1500 VAC continuous (3-way, 2-way for excitation) 
 Input Protection 220 VAC RMS 
 CMRR 160 dB 
 NMRR >80 dB at 60 Hz 
 Input Impedance 1 GOhms.gif (854 bytes) (mV/TC), 55KOhms.gif (854 bytes) (V), 82Ohms.gif (854 bytes) (C) 
 Excitation 150uA(RTD), 1.25V(POT) 
 Output Impedance >10MOhms.gif (854 bytes) (C), ~0Ohms.gif (854 bytes) (V) 
 Output Load 600Ohms.gif (854 bytes) for 4-20mA  
 Power 15-32 VDC @ 25 mA 
 Sensitivity 0.001% F.S. per volt 
 Operating Temp -40C to +75°C 
 Storage Temp -45C to +85°C 
 Certifications UL, cUL, CSA, CE (CL 1, Div. 2 pending) 
 ESD IEC EN61000-4-2 (4KV) 
 Transient IEC EN61000-4-4 (2KV) 
 RFI IEC EN61000-4-8 (10KV/m) 

Power Supply Specifications

 Input Voltage 85 - 265 VAC 50/60 Hz 
 Input Current 260 mA @ 115 VAC for SPS-12W
460 mA @ 115 VAC for SPS-24W
1.2 A @ 115 VAC for SPS-50W
2.4 A @ 115 VAC for SPS-120W
 
 Output Voltage 24 VDC @ 0.5 A for SPS-12W
24 VDC @ 1.0 A for SPS-24W
24 VDC @ 2.1 A for SPS-50 W
24 VDC @ 5.0 A for SPS-120W
 
Switching FRQ. 100 KHz PWM 
 Efficiency 80% 
 Ripple 0.1% RMS MAX 
 Regulation 0.6% (10-100% load) 
 Protection Overcurrent Shutdown plus thermal shutdown 
 Load CAP <8000mF 
 Operation Temp. 0 to 50 C full rated load 
 Storage Temp -40 to +85°C 
 Isolation 3KV input to output
500 V output to ground
 
 Dimensions 90 mm (H) x 18 mm (W) x 102 mm (D) SPS-12W
75 mm (H) x 45 mm (W) x 106 mm (D) SPS-24W
145 mm (H) x 109 mm (W) x 91 mm (D) SPS-50W
200 mm (H) x 225 mm (W) x 125 mm (D) SPS-120W
 
 Approvals UL, CSA, VDE, IEC950
EN55022 Class B
IEC 801-2,3,4,5 level 3
CE
 


SensorPulse Corp. • P.O. Box 8886 • Michigan City, IN 46361 • Ph: (800) 447-5900 or (219) 393-7218 • Fax: (219) 393-7318

© 1998-2002 SensorPulse Corp., All Rights Reserved.
Updated January 2014

This site is owned by a private individual who wishes to keep SensorPulse's website alive and all documentation previously available on it prior to its closing, available to anyone who needs it. No support is provided and everything contained on this site is for information only. Phone Numbers shown on this site may not work and are shown for documentation only. I take no claim of ownership over SensorPulse Corp., only of the domain www.sensorpulse.com. All content on this site is property of SensorPulse Corp. (if they still exist)